Duct Size Calculator
For use by professionals. No warranty; confirm results and design decisions with a licensed engineer. Site Terms
Calculator help
Hi! Ask me anything about using this calculator: what an input means, where to find a value, or why you got a result.
An AI assistant (Claude) that reads this page. It can make mistakes: check important numbers, and confirm design decisions with a licensed engineer.
Step-by-step guide: How to Use the Duct Size Calculator (Ductulator)
Adicot's free online ductulator and duct size calculator sizes round and rectangular ducts for flex, duct board, metal or fabric, by friction loss, velocity or duct dimensions, in US or metric units. It reads the same way as a ductulator wheel: airflow against friction rate gives the round duct, its velocity and the rectangular sizes that match it.
Duct dimensions are always inner dimensions
Every dimension this duct sizer reports is a clear inside dimension. Add liner, wrap or sheet thickness separately when you detail the duct.
Duct sizing chart
The most air each round duct carries at 0.08 and 0.10 in. wg per 100 ft, the low-velocity friction range in the design criteria below. Every figure comes from this calculator's own model, rounded down to the nearest 5 cfm, so in that model the airflow shown keeps the duct at or below the friction rate at the top of its column. Fittings, joints and installation are not included. Velocities are in parentheses. For any other airflow, friction rate, material or a rectangular duct, use the calculator above.
| Round duct | Metal | Flex | ||
|---|---|---|---|---|
| 0.08 in. wg | 0.10 in. wg | 0.08 in. wg | 0.10 in. wg | |
| 4 in. | 30 (344) | 35 (401) | 20 (229) | 25 (286) |
| 5 in. | 60 (440) | 65 (477) | 40 (293) | 50 (367) |
| 6 in. | 95 (484) | 110 (560) | 70 (357) | 80 (407) |
| 7 in. | 145 (543) | 165 (617) | 110 (412) | 120 (449) |
| 8 in. | 210 (602) | 240 (688) | 155 (444) | 175 (501) |
| 9 in. | 290 (656) | 330 (747) | 215 (487) | 240 (543) |
| 10 in. | 385 (706) | 435 (798) | 290 (532) | 320 (587) |
| 12 in. | 630 (802) | 710 (904) | 470 (598) | 525 (668) |
| 14 in. | 950 (889) | 1075 (1006) | 710 (664) | 795 (744) |
| 16 in. | 1360 (974) | 1535 (1099) | 1015 (727) | 1140 (816) |
| 18 in. | 1860 (1053) | 2095 (1186) | 1390 (787) | 1560 (883) |
| 20 in. | 2460 (1128) | 2775 (1272) | 1845 (846) | 2065 (947) |
| 22 in. | 3165 (1199) | 3570 (1352) | 2375 (900) | 2660 (1008) |
| 24 in. | 3990 (1270) | 4495 (1431) | 2995 (953) | 3350 (1066) |
Flex is figured at the calculator's flex roughness. Flex that sags or is compressed carries less air at the same friction rate.
For a version to print, with round ducts to 36 in. and rectangular metal ducts, see the printable duct sizing chart.
Duct size by airflow
Round duct inside diameter for common airflows, from this calculator, before rounding up to a size you can buy. Round up to the next available size, not down. For any other airflow, enter it in the calculator above.
| Airflow | Metal, 0.08 in. wg | Metal, 0.10 in. wg | Flex, 0.08 in. wg |
|---|---|---|---|
| 100 cfm | 6.0 | 5.8 | 6.7 |
| 200 cfm | 7.8 | 7.5 | 8.7 |
| 300 cfm | 9.1 | 8.7 | 10.1 |
| 400 cfm | 10.1 | 9.7 | 11.3 |
| 500 cfm | 11.0 | 10.5 | 12.3 |
| 600 cfm | 11.8 | 11.2 | 13.1 |
| 800 cfm | 13.1 | 12.5 | 14.6 |
| 1,000 cfm | 14.2 | 13.6 | 15.9 |
| 1,200 cfm | 15.3 | 14.6 | 17.0 |
| 1,500 cfm | 16.6 | 15.9 | 18.5 |
| 2,000 cfm | 18.5 | 17.7 | 20.6 |
| 3,000 cfm | 21.5 | 20.6 | 24.0 |
| 4,000 cfm | 24.0 | 23.0 | 26.8 |
| 5,000 cfm | 26.1 | 25.0 | 29.1 |
Duct size by system tonnage
Size on the unit's rated airflow from the manufacturer's data when you have it. This table assumes 400 cfm per ton, a common starting figure, and gives the main supply duct only.
| System | Airflow | Metal, 0.08 in. wg | Metal, 0.10 in. wg | Flex, 0.08 in. wg |
|---|---|---|---|---|
| 1.5 ton | 600 cfm | 11.8 | 11.2 | 13.1 |
| 2 ton | 800 cfm | 13.1 | 12.5 | 14.6 |
| 2.5 ton | 1,000 cfm | 14.2 | 13.6 | 15.9 |
| 3 ton | 1,200 cfm | 15.3 | 14.6 | 17.0 |
| 3.5 ton | 1,400 cfm | 16.2 | 15.5 | 18.0 |
| 4 ton | 1,600 cfm | 17.0 | 16.2 | 19.0 |
| 5 ton | 2,000 cfm | 18.5 | 17.7 | 20.6 |
Round to rectangular duct sizes
The rectangle that carries the same air at the same friction rate as each round duct (its circular equivalent), by duct height. Inside dimensions; round the width up to the next whole inch. Shapes narrower than their height or over 4:1 are left blank. For any other depth, enter it in the calculator above.
| Round duct | 4 in. high | 6 in. high | 8 in. high | 10 in. high | 12 in. high |
|---|---|---|---|---|---|
| 5 in. | 5.3 | ||||
| 6 in. | 7.7 | ||||
| 7 in. | 10.9 | 6.8 | |||
| 8 in. | 14.8 | 9.0 | |||
| 9 in. | 11.6 | 8.5 | |||
| 10 in. | 14.6 | 10.5 | |||
| 12 in. | 22.2 | 15.5 | 12.1 | ||
| 14 in. | 21.8 | 16.7 | 13.7 | ||
| 16 in. | 29.6 | 22.3 | 18.0 | ||
| 18 in. | 29.0 | 23.2 | |||
| 20 in. | 37.0 | 29.3 | |||
| 24 in. | 44.4 |
Duct sizing questions
How many cfm can a 12 × 12 duct handle?
A 12 × 12 in. galvanized metal duct, measured inside, carries the same air at the same friction rate as a 13.1 in. round duct. In this calculator's model that is 800 cfm at 0.08 in. wg per 100 ft (800 fpm), or 905 cfm at 0.10 in. wg (905 fpm). Duct board of the same inside size carries less, because it is rougher. Other rectangular sizes are in the printable duct sizing chart.
How many cfm can a 6, 8 or 10 inch round duct handle?
At 0.08 in. wg per 100 ft, a 6 in. round metal duct carries 95 cfm, an 8 in. 210 cfm and a 10 in. 385 cfm. Flex of the same inside diameter carries less: 70, 155 and 290 cfm, and less again if it sags or is compressed. Other sizes, and the velocities, are in the duct sizing chart above.
How many cfm does a 16 × 8, 20 × 8 or 24 × 8 duct carry?
In galvanized metal, measured inside, at 0.08 in. wg per 100 ft: 16 × 8 in. carries 655 cfm, 20 × 8 in. 860 cfm and 24 × 8 in. 1,065 cfm. At 0.10 in. wg they carry 740, 970 and 1,205 cfm. Every other common size is in the printable duct sizing chart.
What size duct do I need for a given cfm?
It depends on the friction rate or velocity you design to and on the duct material. At 0.08 in. wg per 100 ft, 1,000 cfm needs a 14.2 in. round metal duct and 2,000 cfm needs 18.5 in.; flex needs 15.9 and 20.6 in. The duct size by airflow table above covers 100 to 5,000 cfm. Round up to the next available size, not down. For any other airflow, enter it in the calculator.
What size duct do I need for a 3, 4 or 5 ton system?
Size the duct on the unit's airflow, not its tonnage: use the rated cfm from the manufacturer's data. If you don't have it yet, 400 cfm per ton is a common starting assumption. On that basis, at 0.08 in. wg per 100 ft, a 3-ton system (1,200 cfm) needs a 15.3 in. round metal main, a 4-ton (1,600 cfm) 17.0 in. and a 5-ton (2,000 cfm) 18.5 in., before rounding up. These are the main duct only; branches are sized on each room's airflow.
How do I convert a round duct to a rectangular duct?
Use the rectangle that carries the same air at the same friction rate, its circular equivalent, not the rectangle of the same area, which is too small. A 12 in. round duct becomes 15.5 × 8 in. or 12.1 × 10 in.; a 16 in. round duct 22.3 × 10 in. or 18.0 × 12 in. The round to rectangular table above lists more, and the calculator gives the rectangle for any depth you enter.
What is the rule of thumb for duct sizing?
There is no single rule that replaces a friction or velocity check. For low-velocity comfort ductwork, a friction rate of 0.08 to 0.10 in. wg per 100 ft is common practice. Size on that, then check the velocity against the ranges under design criteria below. Noise or the fan's available static pressure often governs instead. Converting a round duct to a rectangle of the same area under-sizes it (see section 3 of the methodology).
What is a ductulator?
A ductulator is a duct sizing calculator, traditionally a cardboard slide rule or wheel. You line up the airflow in cfm with a friction rate or a velocity and read off the round duct diameter, the velocity, and the rectangular ducts that carry the same air at the same friction rate. This page is an online ductulator: it does the same job by calculation, for more materials, without reading between the marks.
How do I use an online ductulator?
Choose the duct material, enter the airflow, then pick one design criterion (friction loss, velocity, a round diameter or a rectangular size) and enter its value. The results give the exact round duct, then practical round and rectangular sizes, each with its velocity and friction rate. To size by depth, as on the rectangular scale of a ductulator wheel, enter the duct height you have room for under the size buttons. The step-by-step ductulator guide walks through an example.
Is there a free duct sizer I can use without downloading software?
Yes. This page is a free online duct sizer: it does the job of a ductulator wheel or desktop duct sizing software in the browser, with no download, app or sign-up. It sizes round and rectangular metal, flex, duct board and fabric ducts by friction rate, velocity or dimensions, in US or metric units, and works on a phone.
How do I calculate the size of a duct?
From the airflow and either a design velocity or a friction rate. By velocity, use the formula in the next section. By friction rate, the equation has to be solved by iteration, which is what this calculator does.
How do I measure duct size?
Measure the inside. For a round duct, that is the inside diameter; for a rectangular duct, the inside width and height, inside any liner. Flex duct is sold by the diameter of its inner core. This calculator and the charts on this page use inside dimensions throughout.
Duct size formula
By velocity, the round duct diameter follows from the airflow and the velocity you design to:
D = 13.54 × √(Q / V)
Where D is the inside diameter in inches, Q the airflow in cfm and V the velocity in fpm. For example, 400 cfm at 700 fpm needs a 10.2 in. round duct.
By friction rate, which is how a ductulator works, there is no closed-form answer: the diameter and the friction factor depend on each other. The calculator solves the Darcy-Weisbach equation for D, as set out in the methodology below.
HVAC duct sizing calculator methodology
Overview
This duct size calculator sizes HVAC ductwork by the equal friction method, the same principle as a traditional Ductulator, and reports both the round duct and the rectangular duct that carries the same air at the same friction rate. Like a ductulator, this digital duct sizer gives a quick duct size from the airflow and a friction rate or velocity, but it calculates the answer rather than reading it off printed scales. It is based on ASHRAE Fundamentals ch. 21 (and Manual D's circular equivalents), for low- and medium-pressure comfort ductwork at standard air density.
Friction rate is always quoted per 100 ft (per 30 m).
1. Round duct from a friction rate (the ductulator method)
Pressure drop comes from the Darcy-Weisbach equation:
ΔP/L = f × (ρ/2) × V² / D
with the friction factor from the Swamee-Jain (1976) explicit approximation to Colebrook-White, which avoids iterating on f:
f = 0.25 / [log₁₀(ε/3.75D + 5.74/Re^0.9)]²
The constant is written as 3.75 here where the published equation has 3.7. It is inherited from the original workbook and is applied in both directions, so the calculator remains self-consistent; it shifts diameters by a fraction of a percent against the textbook form.
Where:
- ΔP/L = friction loss per unit length (in. wg/100 ft)
- f = Darcy friction factor
- ρ = air density, 0.0735 lb/ft³
- V = air velocity (ft/min)
- D = duct diameter
- ε = absolute roughness of the material
- Re = Reynolds number
Sizing is the same relation solved for D rather than a separate approximation:
D = [8 f L Q² / (π² g hf)]^0.2
Because f depends on D, this converges by iteration, but it converges to the same model the forward direction uses. That matters in practice: size a duct on 0.08 in. wg/100 ft, then enter the diameter you were given, and the calculator returns 0.08.
2. Air velocity
Once the diameter is known, velocity follows from continuity:
V = Q / A, with A = π(D/12)²/4
3. Rectangular duct: equal friction, not equal area
This is the conversion the rectangular scale on a ductulator makes.
Rectangular ducts are reported as the circular equivalent of Huebscher (1948), adopted by ACCA Manual D Appendix 3 and ASHRAE Fundamentals Chapter 21:
De = 1.30 × (W × H)^0.625 / (W + H)^0.25
This holds friction rate and airflow constant, not cross-sectional area. The equal-friction rectangle always has more free area than its round equivalent, and therefore runs at a lower velocity. The calculator reports both velocities so the difference is visible rather than implied.
Sizing a rectangle on equal area instead is a common shortcut and it under-sizes: it gives a duct that carries the air faster and at a higher friction rate than the round duct it was meant to replace.
4. Material roughness
The material sets the absolute roughness ε used above:
| Material | ε |
|---|---|
| Metal (galvanized steel) | 0.0003 ft |
| Duct board | 0.003 ft |
| Flex | 0.00775 ft |
| Fabric | 0.024 ft |
Duct board uses the "medium rough" category value that ASHRAE Fundamentals Chapter 21, Table 1 gives for rigid fibrous glass duct. The table lists its measured range as 0.001 to 0.01 ft and calls it tentative.
Design criteria
These are the ranges most often used in practice. They are guidance, not code requirements. The governing criterion on a real project is usually noise or available static pressure.
Velocity
- Supply ducts: 800–1,500 fpm
- Return ducts: 600–1,000 fpm
- Main supply trunks: 1,000–2,000 fpm
Friction rate
- Low-velocity systems: 0.08–0.10 in. wg/100 ft
- Medium-velocity systems: 0.10–0.20 in. wg/100 ft
- High-velocity systems: 0.20–0.50 in. wg/100 ft
Return air ducts
Return ducts are sized the same way as supply ducts: enter the return airflow and a friction rate or velocity. The velocity ranges above are lower for returns than for supply. A return or transfer opening between rooms is sized with the Return Air Transfer Duct/Pass Thru Calculator.
Worked example
Given: 2,000 CFM, galvanized steel, 0.08 in. wg/100 ft.
Step 1: round duct (ductulator method). Solving Darcy-Weisbach with the Swamee-Jain friction factor at ε = 0.0003 ft gives D = 18.49 in.
Step 2: velocity. A = π(18.49/12)²/4 = 1.865 ft², so V = 2,000 / 1.865 = 1,072 fpm, within the range for a main supply trunk.
Step 3: rectangular equivalent. The square that satisfies De = 1.30 a/2^0.25 at De = 18.49 is 16.92 × 16.92 in., running at 1,006 fpm, slower than the round duct, because the equal-friction rectangle has more free area.
Step 4: constrain the depth. Fix the height at 12 in. and the same duct becomes 24.61 × 12.00 in. at 975 fpm, still at 0.080 in. wg/100 ft.
Note that the equal-area rectangle for an 18.49 in. round duct would be 16.39 in. square. That is the shortcut this calculator does not take.
References
- ASHRAE (2025). ASHRAE Handbook: Fundamentals, Chapter 21: Duct Design. Atlanta: American Society of Heating, Refrigerating and Air-Conditioning Engineers.
- ACCA (2016). Manual D: Residential Duct Systems, Appendix 3: Circular Equivalents. Air Conditioning Contractors of America.
- Huebscher, R.G. (1948). "Friction Equivalents for Round, Square and Rectangular Ducts." ASHVE Transactions, 54: 101–118.
- Swamee, P.K., & Jain, A.K. (1976). "Explicit Equations for Pipe-Flow Problems." Journal of the Hydraulics Division, ASCE, 102(5): 657–664.
- Colebrook, C.F. (1939). "Turbulent Flow in Pipes." Journal of the Institution of Civil Engineers, 11(4): 133–156.
- SMACNA (2006). HVAC Systems Duct Design, 4th Edition. Sheet Metal and Air Conditioning Contractors' National Association.
- Moody, L.F. (1944). "Friction Factors for Pipe Flow." Transactions of the ASME, 66(8): 671–684.
This digital duct size calculator provides estimates comparable to traditional Ductulator tools, offering convenient online duct sizing for HVAC professionals and contractors. It is an estimating aid and does not replace engineering judgment.