Diffuser Size Calculator

For use by professionals. No warranty; confirm results and design decisions with a licensed engineer. Site Terms

Nomenclature

  • Neck velocity: the air velocity through the diffuser's neck, in fpm (m/s).
  • TP: total pressure, in. wg (Pa), for the supply grilles and diffusers; the RA return grilles list negative static pressure (SP).
  • NC: noise criterion. "<20" is below 20; "-" means not rated (quiet).
  • Throw: the distance the air travels before slowing to a terminal velocity, ft (m), listed to 150, 100 and 50 fpm.

Diffuser and grille types

The calculator covers these supply air diffusers and return grilles:

  • 1-way curved blade supply air ceiling diffuser1-way curved blade
  • 2-way curved blade supply air ceiling diffuser2-way curved blade
  • 3-way curved blade supply air ceiling diffuser3-way curved blade
  • 4-way curved blade square supply air ceiling diffuser4-way curved blade
  • Perforated lay-in supply air ceiling diffuserPerforated lay-in
  • Double deflection sidewall supply registerSidewall register
  • Linear bar supply grilleLinear bar grille
  • Fixed blade return air grilleReturn grille

Method

A properly sized diffuser delivers its airflow at a neck velocity that keeps noise and pressure drop acceptable while throwing the air far enough to mix the room. The calculator reads a manufacturer's performance catalog for the type chosen, in the column of the highest catalog velocity at or below the one you enter (no interpolation), and lists every size that:

  1. Carries the airflow: its rated airflow in that column is at least the required airflow;
  2. Is not oversized: its largest rated airflow, at any velocity, is no more than four times the requirement; and
  3. Is not too big at low velocity: its smallest rated airflow is no more than the requirement (1.2 times the requirement at 300 fpm or less).

For 55 cfm or less, the last two become "rated for 55 cfm or less at the lowest velocity" and "smallest rating 55 cfm or less", so the smallest sizes are offered.

If you give a maximum NC, a size is also left out when its NC in that column is above it.

In metric units, the airflow is converted to cfm (1 l/s = 2.11888 cfm, rounded to a whole cfm) and the velocity to fpm (1 m/s = 196.85 fpm), and the catalog is shown converted: airflow in l/s, pressure in Pa (1 in. wg = 249.09 Pa), throw in m.

Example. An AirGuide CB 1-way curved blade diffuser for 200 cfm at 500 fpm: the 500 fpm column gives an 18×4 or 12×6 (200 cfm, NC 24), a 20×4, 14×6 or 10×8 (225 cfm, NC 25), a 24×4, 16×6 or 12×8 (275 cfm, NC 25), an 18×6 or 10×10 (310 cfm, NC 26) and a 30×4, 20×6, 14×8 or 12×10 (350 cfm, NC 26). With a maximum NC of 25, the last two are left out. Drop the velocity to 400 fpm and the 24×4 carries 220 cfm at NC 20.

To size the duct that feeds the diffuser, use the duct size calculator or the printable duct sizing chart.

Choosing a noise criterion

Background sound from HVAC systems should suit the room: quieter for bedrooms, private offices, conference rooms and performance spaces; louder is acceptable in lobbies, corridors and open-plan offices. The ASHRAE Handbook: HVAC Applications, chapter 49, Noise and Vibration Control, Table 1, gives design guidelines for HVAC-related background sound by room type. See the ASHRAE Handbook online.

Note that a diffuser's catalog NC is for a single unit in a standard room; several diffusers in one space add up, and the room's absorption changes what is heard.

Notes on the catalogs

  • The catalogs are sample manufacturer data (AirGuide), for preliminary selection. Confirm the final selection, and the pressure and throw, with your manufacturer's data.
  • The AirGuide data are from AirGuide Manufacturing's performance data sheets: RA fixed blade return grilles, V/VH supply grilles and registers (sidewall, at 0°, 22½° and 45° blade deflection), CB curved blade supply grilles and registers (1- to 4-way), AVP-T louvered lay-in diffusers (1- and 4-way, square neck) and PS perforated lay-in diffusers (1- to 4-way, round neck), both in a 24 × 24 in. ceiling panel. Their throws are given at terminal velocities of 150, 100 and 50 fpm. The LD linear bar grilles are rated per foot of diffuser length, at 0° and 15° deflection, with side wall and sill or floor throws. The AirGuide sheets have a few evident misprints (a throw that falls as velocity rises, such as 20-3-49 for 20-30-49); these are shown as printed.
  • The CB 1- to 4-way patterns share airflow, NC and pressure ratings; only the throws differ.

Adicot is not affiliated with, and does not recommend, any diffuser or grille manufacturer. Any references or links to specific manufacturers are for illustration only.

Top