Ventilation Rates: ASHRAE 62.1, IMC, FBC, ASHRAE 170 and 62.2

Type part of a name, such as “exam”, or open the list to browse.

Units
Zone (optional)

Occupants start at the table’s default occupant density times the floor area. Type your own number to override it; clear it to go back to the default.

Results

Ventilation rates and zone outdoor airflow
Exhaust rates

ANSI/ASHRAE Standard 62.1-2025, Table 6-1 (minimum ventilation rates in the breathing zone), Normative Appendix E Table E-1 (outpatient health care) and Table 6-2 (minimum exhaust rates).

How to use it

Review the methodology below to make sure it aligns with your project's requirements, then:

  1. Choose the standard or code: ASHRAE 62.1-2025, the 2024 IMC, the Florida Building Code, Mechanical (2023 or 2026 edition), ASHRAE 170-2021 for inpatient health care spaces, or ASHRAE 62.2-2025 for dwelling units.
  2. Choose the occupancy category or space. Type any part of its name, such as “exam” or “locker”, to narrow the list, or open the list to browse every entry under its heading.
  3. The table's rates for that space appear in the results, with the notes that apply.
  4. Optionally, enter the floor area (and, for ASHRAE 170, the ceiling height; for 62.2, the number of bedrooms) to turn the rates into airflow. For 62.1 and the IMC, enter the number of occupants if you know it; otherwise the table's default occupant density is used.

The calculator remembers your last entries in this browser. Use Copy link to these results to save or share a calculation.

Methodology

ANSI/ASHRAE Standard 62.1, Ventilation and Acceptable Indoor Air Quality, sets minimum ventilation rates for commercial and institutional buildings by occupancy category. This calculator uses the 2025 edition, and three of its tables:

  • Table 6-1, Minimum Ventilation Rates in Breathing Zone: the people outdoor air rate Rp, the area outdoor air rate Ra, the default occupant density, the air class, whether the space may use occupied-standby (OS, Section 6.2.6.2), and the maximum CO2 above ambient, ΔC6.1, used for CO2-based demand-controlled ventilation. "NA" means the standard gives no CO2 limit for that space.
  • Table E-1 (Normative Appendix E), outpatient health care: the same rates for outpatient spaces the authority having jurisdiction has deemed Standard 170 not to cover.
  • Table 6-2, Minimum Exhaust Rates: exhaust per unit (per kitchen, toilet room, fixture or shower head), per floor area, or both, and the air class. The requirements tied to particular spaces (auto repair, parking garages, commercial kitchens, laboratories, toilets) are shown with the result, with their section numbers.

The 2025 edition changed more than its layout. It lowered the default occupant density for many spaces (restaurant dining 70 to 67, casinos 120 to 91, beauty and nail salons 25 to 7, for example), cut science laboratory exhaust from 1.00 to 0.35 cfm/ft², added rows such as educational corridors and information technology equipment rooms and a Residential heading, renamed others, and replaced Table 6-2's lettered notes with continuous and intermittent rates and requirements in Section 6.5. Paint spray booths and refrigerating machinery rooms moved to Table 6-3 (airstreams), which gives only an air class.

A dash (—) is the standard's "not applicable". The metric rates are the standard's own metric values, which are rounded, not exact conversions of the inch-pound values.

Breathing-zone outdoor airflow

The Ventilation Rate Procedure's breathing-zone outdoor airflow (Equation 6-1) is

Vbz = Rp × Pz + Ra × Az

where:

  • Vbz = breathing-zone outdoor airflow, cfm (L/s)
  • Rp = people outdoor air rate, cfm/person (L/s·person)
  • Pz = zone population, the largest number of people expected to occupy the zone in typical usage
  • Ra = area outdoor air rate, cfm/ft² (L/s·m²)
  • Az = zone floor area, ft² (m²)

Where the population is not known, Pz is the default occupant density times the floor area: per 1,000 ft², or per 100 m².

Vbz is the breathing-zone requirement only. The zone and system outdoor air intake also depend on the zone air distribution effectiveness and the system ventilation efficiency, which this calculator does not apply.

Exhaust

The minimum exhaust depends on the category and may be given per unit, per floor area, or both. Where a rate is given per floor area, the calculator multiplies it by the zone's floor area. Dwelling-unit kitchens, shower rooms and toilets have two per-unit rates, shown as a pair such as 50/70 cfm: the first for continuous operation, the second for intermittent operation, which is intended to run whenever the space is in use.

Worked examples

Retail, pet shop (animal areas), 2,000 ft². Table 6-1 gives Rp = 7.5 cfm/person, Ra = 0.18 cfm/ft², a default density of 10 people per 1,000 ft² and air class 2.

  • Pz = 2,000 ft² × 10 / 1,000 ft² = 20 people
  • Vbz = 7.5 × 20 + 0.18 × 2,000 = 150 + 360 = 510 cfm

Table 6-2 gives 0.90 cfm/ft², air class 2, so the minimum exhaust is 0.90 × 2,000 = 1,800 cfm.

Office space, 5,000 ft². Table 6-1 gives Rp = 5 cfm/person, Ra = 0.06 cfm/ft², a default density of 5 people per 1,000 ft², air class 1, occupied-standby allowed and a maximum CO2 of 600 ppm above ambient.

  • Pz = 5,000 ft² × 5 / 1,000 ft² = 25 people
  • Vbz = 5 × 25 + 0.06 × 5,000 = 125 + 300 = 425 cfm

Soiled laundry storage room, 500 ft². Table 6-2 gives 1.00 cfm/ft² and air class 3, so the minimum exhaust is 1.00 × 500 = 500 cfm.

Air classes

The standard classes air by its contaminant concentration, sensory-irritation intensity and odor, and limits where each class may be recirculated or transferred:

  • Class 1: low contaminant concentration, low sensory-irritation intensity and inoffensive odor.
  • Class 2: moderate contaminant concentration, mild sensory-irritation intensity or mildly offensive odors.
  • Class 3: significant contaminant concentration, significant sensory-irritation intensity or offensive odor.
  • Class 4: highly objectionable fumes or gases, or potentially dangerous particles, bioaerosols or gases.

Considerations

  • Actual occupancy. The default densities are for when the actual occupancy is not known. Use the design occupancy when you have it.
  • Supply and exhaust. Some spaces have both a Table 6-1 ventilation rate and a Table 6-2 exhaust rate; the results show both.
  • Outpatient health care. These rates are from Normative Appendix E of Standard 62.1-2025, for spaces in outpatient facilities the authority having jurisdiction has deemed ASHRAE/ASHE Standard 170 not to cover. The dental rates are intended only for outpatient dental clinics where the amount of nitrous oxide is limited, not for dental operatories in institutional buildings where nitrous oxide is piped.
  • Airborne infection. The standard notes that the outpatient rates provide for acceptable indoor air quality; they do not address the airborne transmission of viruses, bacteria and other infectious contagions.
  • Laboratories and animal facilities. Laboratories that comply with ANSI/ASSP Z9.5, and animal facilities with a risk evaluation by the owner's environmental health and safety professional, need not meet the Table 6-1 and 6-2 rates (Sections 6.2.1.1.4 and 6.2.1.1.5).
  • Codes. This is for education and reference. Always consult the complete ASHRAE Standard 62.1, the edition your code adopts, and the applicable local codes for design and compliance.

Other standards and codes

2024 IMC and the Florida Building Code, Mechanical

The International Mechanical Code sets its own minimum ventilation rates in Table 403.3.1.1, with the same breathing-zone equation as ASHRAE 62.1 (IMC Equation 4-1): Vbz = Rp × Pz + Ra × Az. The table also gives the exhaust rate for each occupancy, per square foot of floor area or, where a note says so, per room or per fixture. The IMC's categories and some rates differ from ASHRAE 62.1, so use the table your jurisdiction has adopted.

Florida adopts the IMC with amendments as the Florida Building Code, Mechanical. The 2026 Ninth Edition (based on the 2024 IMC) has the same Table 403.3.1.1 values as the 2024 IMC. The 2023 Eighth Edition (based on the 2021 IMC) has fewer categories: it has no animal facilities or outpatient health care rows, for example. The IMC and FBC tables are in inch-pound units only.

ASHRAE 170-2021, inpatient health care

ANSI/ASHRAE/ASHE Standard 170, Ventilation of Health Care Facilities, sets design parameters for each space in Table 7-1: the pressure relationship to adjacent areas, the minimum outdoor and total air changes per hour, whether all room air must be exhausted directly outdoors, whether room recirculating units are allowed, unoccupied turndown, minimum filter efficiency, and the design relative humidity and temperature. Given the floor area and ceiling height, the calculator converts the air change rates to airflow:

Q = ach × room volume / 60, in cfm (ft³), or ach × room volume / 3.6, in L/s (m³)

The notes shown with each space are short summaries. Read the full note in the standard before relying on it. Outpatient spaces (Table 8-1) and residential health care (Table 9-1) are not included.

ASHRAE 62.2-2025, dwelling units

ANSI/ASHRAE Standard 62.2, Ventilation and Acceptable Indoor Air Quality in Residential Buildings, sets the continuous whole-dwelling ventilation rate (Equation 4-1):

Qtot = 0.03 Afloor + 7.5 (Nbr + 1), in cfm, with Afloor in ft²; or 0.15 Afloor + 3.5 (Nbr + 1), in L/s, with Afloor in m²

where Nbr is the number of bedrooms, not less than 1. For example, a 2,000 ft² three-bedroom house needs 0.03 × 2,000 + 7.5 × 4 = 90 cfm. The standard also sets local exhaust for kitchens, bathrooms and toilet rooms (Tables 5-1 and 5-2), shown with the result. Its infiltration credit (Section 4.1.2), which needs a blower door test, is not applied.

Table 6-1: Minimum ventilation rates in breathing zone

From ANSI/ASHRAE Standard 62.1-2025. A blank cell is one the standard leaves blank.

Occupancy categoryRp cfm/personRp L/s·personRa cfm/ft²Ra L/s·m²Default density, #/1,000 ft² (#/100 m²)Air classOS (6.2.6.2)Max. CO2 above ambient, ppm
Animal Facilities-Animal exam room (veterinary office)1050.120.6202NA
Animal Facilities-Animal imaging (MRI/CT/PET)1050.180.9203NA
Animal Facilities-Animal operating rooms1050.180.9203NA
Animal Facilities-Animal postoperative recovery room1050.180.9203NA
Animal Facilities-Animal preparation rooms1050.180.9203NA
Animal Facilities-Animal procedure room1050.180.9203NA
Animal Facilities-Animal surgery scrub1050.180.9203NA
Animal Facilities-Large-animal holding room1050.180.9203NA
Animal Facilities-Necropsy1050.180.9203NA
Animal Facilities-Small-animal-cage room (static cages)1050.180.9203NA
Animal Facilities-Small-animal-cage room (ventilated cages)1050.180.9203NA
Correctional Facilities-Booking/waiting7.53.80.060.35021200
Correctional Facilities-Cell52.50.120.6252NA
Correctional Facilities-Dayroom52.50.060.33011500
Correctional Facilities-Guard stations52.50.060.31511200
Educational Facilities-Art classroom1050.180.9202NA
Educational Facilities-Assembly without fixed seats—concentrated (chairs only—fixed)7.53.80.060.3651✓1200
Educational Facilities-Classrooms (ages 5 to 8)1050.120.6251600
Educational Facilities-Classrooms (age 9+)1050.120.6351600
Educational Facilities-Corridors (ages 5+)——0.120.6—1NA
Educational Facilities-Daycare sickroom1050.180.9253NA
Educational Facilities-Daycare (through age 4)1050.180.9252NA
Educational Facilities-Information technology equipment facilities (occupiable)1050.120.6251600
Educational Facilities-Lecture hall (fixed seats)7.53.80.060.31431✓1200
Educational Facilities-Libraries52.50.120.610600
Educational Facilities-Media center1050.120.6251600
Educational Facilities-Multiuse assembly (tables and chairs)7.53.80.060.3671✓1200
Educational Facilities-Music/theater/dance1050.060.3351✓2100
Educational Facilities-Science laboratories1050.180.9252NA
Educational Facilities-University/college laboratories1050.180.9252NA
Educational Facilities-Wood/metal shop1050.180.9202NA
Food and Beverage Service-Bars, cocktail lounges7.53.80.180.910021200
Food and Beverage Service-Cafeteria/fast-food dining7.53.80.180.9672900
Food and Beverage Service-Kitchen (cooking)7.53.80.120.652NA
Food and Beverage Service-Restaurant dining rooms7.53.80.180.96721500
General-Break rooms52.50.060.3251✓1500
General-Coffee stations52.50.060.3201✓1200
General-Conference/meeting52.50.060.3501✓1500
General-Corridors——0.060.3—1✓NA
General-Occupiable storage rooms for liquids or gels52.50.120.622NA
Hotels, Motels, Resorts, Dormitories-Barracks sleeping areas52.50.060.3201✓900
Hotels, Motels, Resorts, Dormitories-Bedroom/living room52.50.060.3101✓600
Hotels, Motels, Resorts, Dormitories-Laundry rooms, central52.50.120.6102NA
Hotels, Motels, Resorts, Dormitories-Laundry rooms within dwelling units52.50.120.6101NA
Hotels, Motels, Resorts, Dormitories-Lobbies/prefunction7.53.80.060.3301✓1500
Hotels, Motels, Resorts, Dormitories-Multipurpose assembly52.50.060.31201✓1800
Miscellaneous Spaces-Banks or bank lobbies7.53.80.060.3151✓900
Miscellaneous Spaces-Bank vaults/safe deposit52.50.060.352✓600
Miscellaneous Spaces-Freezer and refrigerated spaces (<50°F [10°C])1050002NA
Miscellaneous Spaces-Information technology equipment facilities (occupiable)52.50.060.331✓NA
Miscellaneous Spaces-Manufacturing where hazardous materials are not used1050.180.972600
Miscellaneous Spaces-Manufacturing where hazardous materials are used (excludes heavy industrial and chemical processes)1050.180.973NA
Miscellaneous Spaces-Pharmacy (prep. area)52.50.180.9102900
Miscellaneous Spaces-Photo studios52.50.120.6101NA
Miscellaneous Spaces-Shipping/receiving1050.120.622700
Miscellaneous Spaces-Sorting, packing, light assembly7.53.80.120.672900
Miscellaneous Spaces-Telephone closets——00—1NA
Miscellaneous Spaces-Transportation waiting7.53.80.060.3671✓1800
Miscellaneous Spaces-Warehouses1050.060.3—2700
Office Buildings-Main entry lobbies52.50.060.3101✓1200
Office Buildings-Occupiable storage rooms for dry materials52.50.060.321700
Office Buildings-Office space52.50.060.351✓600
Office Buildings-Reception areas52.50.060.3301✓2100
Office Buildings-Telephone/data entry52.50.060.3601✓1800
Public Assembly Spaces-Auditorium seating area52.50.060.31431✓1800
Public Assembly Spaces-Courtrooms52.50.060.3701✓1500
Public Assembly Spaces-Legislative chambers52.50.060.3501✓1800
Public Assembly Spaces-Libraries52.50.120.6101600
Public Assembly Spaces-Lobbies52.50.060.31501✓1800
Public Assembly Spaces-Museums (children’s)7.53.80.120.64011800
Public Assembly Spaces-Museums/galleries7.53.80.060.3331✓1500
Public Assembly Spaces-Places of religious worship52.50.060.31201✓1800
Residential-Common corridors——0.060.31✓NA
Retail-Sales (except as below)7.53.80.120.6152900
Retail-Barbershop7.53.80.060.372✓NA
Retail-Beauty and nail salons20100.120.672NA
Retail-Coin-operated laundries7.53.80.120.672NA
Retail-Mall common areas7.53.80.060.3331✓2100
Retail-Pet shops (animal areas)7.53.80.180.9102NA
Retail-Supermarket7.53.80.060.381✓1500
Sports and Entertainment-Bowling alley (seating)1050.120.6401900
Sports and Entertainment-Disco/dance floors20100.060.31002✓1500
Sports and Entertainment-Gambling casinos7.53.80.180.99111200
Sports and Entertainment-Game arcades7.53.80.180.9201900
Sports and Entertainment-Gym, sports arena (play area)20100.180.972900
Sports and Entertainment-Health club/aerobics room20100.060.32021200
Sports and Entertainment-Health club/weight rooms20100.060.31021500
Sports and Entertainment-Spectator areas7.53.80.060.31431✓1500
Sports and Entertainment-Stages, studios1050.060.3671✓1500
Sports and Entertainment-Swimming (pool and deck)——0.482.4—2NA

Table E-1: Outpatient health care facilities

From ANSI/ASHRAE Standard 62.1-2025, Normative Appendix E, for outpatient spaces the authority having jurisdiction has deemed Standard 170 not to cover.

Occupancy categoryRp cfm/personRp L/s·personRa cfm/ft²Ra L/s·m²Default density, #/1,000 ft² (#/100 m²)Air class
Birthing room1050.180.9152
Class 1 imaging rooms7.53.80.120.651
Dental operatory1050.180.9201
General examination room7.53.80.120.6201
Other dental treatment areas52.50.060.351
Physical therapy exercise area20100.180.972
Physical therapy individual room1050.120.6202
Physical therapeutic pool area——0.482.4—3
Prosthetics and orthotics room1050.180.9202
Psychiatric consultation room52.50.060.3201
Psychiatric examination room52.50.060.3201
Psychiatric group room52.50.060.3501
Psychiatric seclusion room1050.120.651
Speech therapy room52.50.060.3201
Urgent care examination room7.53.80.120.6202
Urgent care observation room52.50.060.3202
Urgent care treatment room7.53.80.120.6202
Urgent care triage room1050.180.9203

Table 6-2: Minimum exhaust rates

From ANSI/ASHRAE Standard 62.1-2025. A pair such as 50/100 is the continuous / intermittent operation rate.

Occupancy categorycfm/unitcfm/ft²L/s·unitL/s·m²Air class
Animal Facilities-Animal imaging (MRI/CT/PET)—0.9—4.53
Animal Facilities-Animal operating rooms—3—153
Animal Facilities-Animal postoperative recovery room—1.5—7.53
Animal Facilities-Animal preparation rooms—1.5—7.53
Animal Facilities-Animal procedure room—2.25—11.33
Animal Facilities-Animal surgery scrub—1.5—7.53
Animal Facilities-Large-animal holding room—2.25—11.33
Animal Facilities-Necropsy—2.25—11.33
Animal Facilities-Small-animal-cage room (static cages)—2.25—11.33
Animal Facilities-Small-animal-cage room (ventilated cages)—1.5—7.53
Arenas—0.5——1
Educational Facilities-Art classroom—0.7—3.52
Auto repair rooms—1.5—7.52
Retail-Barbershop—0.5—2.52
Retail-Beauty and nail salons—0.6—32
Correctional Facilities-Cell—1—52
Copy, printing rooms—0.5—2.52
Darkrooms—1—52
Dwelling-unit kitchens50/100—25/50—2
Janitor closets, trash rooms, recycling—1—53
Kitchenettes—0.3—1.52
Kitchens—commercial—0.7—3.52
Locker rooms for athletic, industrial, and health care facilities—0.5—2.52
All other locker rooms—0.25—1.252
Shower rooms per shower head20/50—10/25—2
Parking garages—0.75—3.72
Retail-Pet shops (animal areas)—0.9—4.52
Educational Facilities-Science laboratories—0.35—1.752
Soiled laundry storage rooms—1—53
Storage rooms, chemical—1.5—7.54
Toilets—private (one person)25/50—12.5/25—2
Toilets—public (>1 person) per fixture (water closet or urinal)50/70—25/35—2
Woodwork shop/classrooms—0.5—2.52

2024 IMC Table 403.3.1.1: Minimum ventilation rates

From the 2024 International Mechanical Code (also the 2026 Florida Building Code, Mechanical, Ninth Edition). Exhaust rates are cfm/ft² unless a note (e, f) makes them per fixture or per room.

Occupancy classificationNotesOccupant density, #/1,000 ft²Rp cfm/personRa cfm/ft²Exhaust, cfm/ft²
Animal facilities: Animal exam room (veterinary office)20100.12—
Animal facilities: Animal imaging (MR/CT/PET)20100.180.9
Animal facilities: Animal operating rooms20100.183
Animal facilities: Animal postoperative recovery room20100.181.5
Animal facilities: Animal preparation rooms20100.181.5
Animal facilities: Animal procedure room20100.182.25
Animal facilities: Animal surgery scrub20100.181.5
Animal facilities: Large-animal holding room20100.182.25
Animal facilities: Necropsy20100.182.25
Animal facilities: Small-animal cage room (static cages)20100.182.25
Animal facilities: Small-animal cage room (ventilated cages)20100.181.5
Correctional facilities: Booking/waiting507.50.06—
Correctional facilities: Cells, without plumbing fixtures2550.12—
Correctional facilities: Cells, with plumbing fixturesg2550.121
Correctional facilities: Day room3050.06—
Correctional facilities: Guard stations1550.06—
Dry cleaners, laundries: Coin-operated dry cleaner2015——
Dry cleaners, laundries: Coin-operated laundries207.50.12—
Dry cleaners, laundries: Commercial dry cleaner3030——
Dry cleaners, laundries: Commercial laundry1050.12—
Dry cleaners, laundries: Storage, pick up307.50.12—
Education: Art classroomg20100.180.7
Education: Auditoriums15050.06—
Education: Classrooms (ages 5–8)25100.12—
Education: Classrooms (age 9 plus)35100.12—
Education: Computer lab25100.12—
Education: Day care (through age 4)25100.18—
Education: Lecture classroom657.50.06—
Education: Lecture hall (fixed seats)1507.50.06—
Education: Locker/dressing roomsg———0.25
Education: Media center25100.12—
Education: Multiuse assembly1007.50.06—
Education: Music/theater/dance35100.06—
Education: Science laboratoriesg25100.181
Education: Smoking loungesb7060——
Education: Sports locker roomsg———0.5
Education: Wood/metal shopsg20100.180.5
Food and beverage service: Bars, cocktail lounges1007.50.18—
Food and beverage service: Break rooms2550.06—
Food and beverage service: Cafeteria, fast food1007.50.18—
Food and beverage service: Coffee stations2050.06—
Food and beverage service: Corridors——0.06—
Food and beverage service: Dining rooms707.50.18—
Food and beverage service: Kitchens (cooking)b207.50.120.7
Food and beverage service: Occupiable storage rooms for liquids or gels250.12—
Hotels, motels, resorts and dormitories: Bathrooms/toilet—privateg, f———25/50
Hotels, motels, resorts and dormitories: Bedroom/living room1050.06—
Hotels, motels, resorts and dormitories: Conference/meeting5050.06—
Hotels, motels, resorts and dormitories: Dormitory sleeping areas2050.06—
Hotels, motels, resorts and dormitories: Gambling casinos1207.50.18—
Hotels, motels, resorts and dormitories: Laundry rooms, central1050.12—
Hotels, motels, resorts and dormitories: Laundry rooms within dwelling units1050.12—
Hotels, motels, resorts and dormitories: Lobbies/prefunction307.50.06—
Hotels, motels, resorts and dormitories: Multipurpose assembly12050.06—
Offices: Break rooms5050.12—
Offices: Conference rooms5050.06—
Offices: Main entry lobbies1050.06—
Offices: Occupiable storage rooms for dry materials250.06—
Offices: Office spaces550.06—
Offices: Reception areas3050.06—
Offices: Telephone/data entry6050.06—
Outpatient healthcare facilities: Birthing roomi, j15100.18—
Outpatient healthcare facilities: Class 1 imaging roomi, j550.12—
Outpatient healthcare facilities: Dental operatoryi, j, k20100.18—
Outpatient healthcare facilities: General examination roomi, j207.50.12—
Outpatient healthcare facilities: Other dental treatment areasi, j550.06—
Outpatient healthcare facilities: Physical therapy exercise areai, j7200.18—
Outpatient healthcare facilities: Physical therapy individual roomi, j20100.06—
Outpatient healthcare facilities: Physical therapeutic pool areai, j——0.48—
Outpatient healthcare facilities: Prosthetics and orthotics roomi, j20100.18—
Outpatient healthcare facilities: Psychiatric consultation roomi, j2050.06—
Outpatient healthcare facilities: Psychiatric examination roomi, j2050.06—
Outpatient healthcare facilities: Psychiatric group roomi, j5050.06—
Outpatient healthcare facilities: Psychiatric seclusion roomi, j5100.06—
Outpatient healthcare facilities: Speech therapy roomi, j2050.06—
Outpatient healthcare facilities: Urgent care examination roomi, j207.50.12—
Outpatient healthcare facilities: Urgent care observation roomi, j2050.06—
Outpatient healthcare facilities: Urgent care treatment roomi, j207.50.18—
Outpatient healthcare facilities: Urgent care triage roomi, j20100.18—
Private dwellings, single and multiple: Garages, common for multiple unitsb———0.75
Private dwellings, single and multiple: Kitchensb, f———50/100
Private dwellings, single and multiple: Living areascBased on number of bedrooms. First bedroom, 2; each additional bedroom, 10.35 ACH but not less than 15 cfm/person——
Private dwellings, single and multiple: Toilet rooms and bathroomsg, f———25/50
Public spaces: Corridors——0.06—
Public spaces: Courtrooms7050.06—
Public spaces: Elevator car———1
Public spaces: Legislative chambers5050.06—
Public spaces: Libraries1050.12—
Public spaces: Museums (children’s)407.50.12—
Public spaces: Museums/galleries407.50.06—
Public spaces: Places of religious worship12050.06—
Public spaces: Room with adult changing statione———50/70
Public spaces: Shower room (per shower head)g, f———50/20
Public spaces: Smoking loungesb7060——
Public spaces: Toilet rooms — publicg, e———50/70
Retail stores, sales floors and showroom floors: Dressing rooms———0.25
Retail stores, sales floors and showroom floors: Mall common areas407.50.06—
Retail stores, sales floors and showroom floors: Sales157.50.12—
Retail stores, sales floors and showroom floors: Shipping and receiving2100.12—
Retail stores, sales floors and showroom floors: Smoking loungesb7060——
Retail stores, sales floors and showroom floors: Storage rooms——0.12—
Retail stores, sales floors and showroom floors: Warehouses (see “Storage”)—100.06—
Specialty shops: Automotive motor fuel-dispensing stationsb———1.5
Specialty shops: Banks or lobbies157.50.06—
Specialty shops: Barber257.50.060.5
Specialty shops: Beauty salonsb25200.120.6
Specialty shops: Embalming roomb———2
Specialty shops: Nail salonsb, h25200.120.6
Specialty shops: Pet shops (animal areas)b107.50.180.9
Specialty shops: Supermarkets87.50.06—
Sports and amusement: Bowling alleys (seating areas)40100.12—
Sports and amusement: Disco/dance floors100200.06—
Sports and amusement: Game arcades207.50.18—
Sports and amusement: Gym, stadium, arena (play area)7200.18—
Sports and amusement: Health club/aerobics room40200.06—
Sports and amusement: Health club/weight room10200.06—
Sports and amusement: Ice arenas without combustion engines——0.30.5
Sports and amusement: Spectator areas1507.50.06—
Sports and amusement: Swimming pools (pool and deck area)——0.48—
Storage: Refrigerated warehouses/freezers (< 50°F)—10——
Storage: Repair garages, enclosed parking garagesb, d———0.75
Storage: Warehousesl—100.06—
Theaters: Lobbies15050.06—
Theaters: Stages, studios70100.06—
Theaters: Ticket booths6050.06—
Transportation: Platforms1007.50.06—
Transportation: Transportation waiting1007.50.06—
Workrooms: Bank vaults/safe deposit550.06—
Workrooms: Computer (without printing)450.06—
Workrooms: Copy, printing rooms450.060.5
Workrooms: Darkrooms———1
Workrooms: Manufacturing where hazardous materials are not used7100.18—
Workrooms: Manufacturing where hazardous materials are used (excludes heavy industrial and chemical processes)7100.18—
Workrooms: Meat processingc1015——
Workrooms: Pharmacy (prep. area)1050.18—
Workrooms: Photo studios1050.12—
Workrooms: Sorting, packing, light assembly77.50.12—
Workrooms: Telephone closets——0—

References

American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE). ANSI/ASHRAE Standard 62.1-2025: Ventilation and Acceptable Indoor Air Quality. Atlanta, GA: ASHRAE.

International Code Council (ICC). 2024 International Mechanical Code, Chapter 4: Ventilation.

Florida Building Commission. 2023 Florida Building Code, Mechanical, Eighth Edition and 2026 Florida Building Code, Mechanical, Ninth Edition, Chapter 4.

ASHRAE and ASHE. ANSI/ASHRAE/ASHE Standard 170-2021: Ventilation of Health Care Facilities. Atlanta, GA: ASHRAE.

ASHRAE. ANSI/ASHRAE Standard 62.2-2025: Ventilation and Acceptable Indoor Air Quality in Residential Buildings. Atlanta, GA: ASHRAE.