Ohm's Law with Power Calculator
For use by professionals. No warranty; confirm results and design decisions with a licensed engineer. Site Terms
Calculator help
Hi! Ask me anything about using this calculator: what an input means, where to find a value, or why you got a result.
An AI assistant (Claude) that reads this page. It can make mistakes: check important numbers, and confirm design decisions with a licensed engineer.
Click here to provide feedback on this calculator
Your current inputs are sent with it, so we can see what you saw.
Common values
The tables below are for single-phase resistive loads, such as electric heaters and reheat coils. For any other value, use the calculator above.
Watts to amps at 120, 208, 240 and 277 volts
I = P ÷ V, so divide the watts by the voltage.
| Watts | Amps at 120 V | Amps at 208 V | Amps at 240 V | Amps at 277 V |
|---|---|---|---|---|
| 500 | 4.2 | 2.4 | 2.1 | 1.8 |
| 1,000 | 8.3 | 4.8 | 4.2 | 3.6 |
| 1,500 | 12.5 | 7.2 | 6.3 | 5.4 |
| 2,000 | 16.7 | 9.6 | 8.3 | 7.2 |
| 3,000 | 25.0 | 14.4 | 12.5 | 10.8 |
| 4,000 | 33.3 | 19.2 | 16.7 | 14.4 |
| 4,500 | 37.5 | 21.6 | 18.8 | 16.2 |
| 5,000 | 41.7 | 24.0 | 20.8 | 18.1 |
| 7,500 | 62.5 | 36.1 | 31.3 | 27.1 |
| 10,000 | 83.3 | 48.1 | 41.7 | 36.1 |
kW to ohms at 120, 208, 240 and 277 volts
R = V² ÷ P, with P in watts.
| kW | Ohms at 120 V | Ohms at 208 V | Ohms at 240 V | Ohms at 277 V |
|---|---|---|---|---|
| 1 | 14.4 | 43.3 | 57.6 | 76.7 |
| 1.5 | 9.6 | 28.8 | 38.4 | 51.2 |
| 2 | 7.2 | 21.6 | 28.8 | 38.4 |
| 3 | 4.8 | 14.4 | 19.2 | 25.6 |
| 4.5 | 3.2 | 9.6 | 12.8 | 17.1 |
| 5 | 2.9 | 8.7 | 11.5 | 15.3 |
| 7.5 | 1.9 | 5.8 | 7.7 | 10.2 |
| 10 | 1.4 | 4.3 | 5.8 | 7.7 |
Methodology
This calculator determines electrical power, voltage, current and resistance for HVAC systems, motors and control circuits.
Ohm's law defines the linear relationship between voltage (V), current (I) and resistance (R):
V = I × R
When power (P) is introduced, the set of equations expands to:
P = V × I = I² × R = V² ÷ R
These formulas let engineers estimate current and resistance for resistive loads such as electric heaters, and the heat output of resistive HVAC elements. They hold exactly only for resistive loads: motors and other inductive loads also need their power factor, and three-phase loads a factor of √3. Conductor and breaker sizing follow the NEC.
Calculation methods
Depending on which two quantities are known, the calculator applies:
| Known values | Calculations performed |
|---|---|
| Voltage (V), current (I) | P = V × I, R = V ÷ I |
| Voltage (V), resistance (R) | I = V ÷ R, P = V × I |
| Voltage (V), power (P) | I = P ÷ V, R = V ÷ I |
| Current (I), resistance (R) | V = I × R, P = V × I |
| Current (I), power (P) | V = P ÷ I, R = V ÷ I |
| Power (P), resistance (R) | I = √(P ÷ R), V = I × R |
Worked example
Given: a 208-volt electric duct heater rated at 4,500 watts. Find the operating current and resistance.
- I = P ÷ V = 4,500 ÷ 208 = 21.63 amps
- R = V ÷ I = 208 ÷ 21.635 = 9.61 ohms (with the unrounded current; 208 ÷ 21.63 would give 9.62)
This matches standard calculations for single-phase resistive HVAC loads, such as electric coils or reheat elements.
Further reading
- National Fire Protection Association (NFPA). NFPA 70: National Electrical Code (NEC), 2026 edition.
- ASHRAE. Standard 90.1-2025: Energy Standard for Sites and Buildings Except Low-Rise Residential Buildings.
FAQs
How do I calculate power from voltage and resistance?
Square the voltage and divide by the resistance: P = V² ÷ R. For example, 120 volts across 460 ohms gives 120² ÷ 460 = 31.3 watts.
How do I convert kW to ohms?
For a resistive load, R = V² ÷ P, with P in watts. A 4.5 kW heater element at 240 volts has a resistance of 240² ÷ 4,500 = 12.8 ohms. The voltage is needed: the same 4.5 kW at 208 volts is 9.6 ohms.
How many amps does a 1,500-watt heater draw at 120 volts?
I = P ÷ V = 1,500 ÷ 120 = 12.5 amps. This holds for resistive loads such as heaters; motors and other inductive loads also need their power factor.
Does Ohm's law work for three-phase loads?
Not with the single-phase formulas. A balanced three-phase resistive load draws I = P ÷ (√3 × V), with V the line-to-line voltage. A 10 kW three-phase heater at 208 volts draws 10,000 ÷ (1.732 × 208) = 27.8 amps. This calculator uses the single-phase formulas.