Condensate Converter

Entered in

Results

Enter a value to convert.

Latent heat and water removed are linked by 1.04 lb per pint and 1,055 Btu per lb of water condensed.

This converter converts moisture measurement units, such as latent Btu/h and kW, pints per day, gallons per hour and liters per hour.

How to use it

Review the methodology below to make sure it aligns with your project's requirements, then:

  1. Enter the value to convert.
  2. Choose its unit: Btu/h, watts, kW, pints per day, gallons per hour, liters per hour or pounds per hour.
  3. The value appears in every unit in the results, and updates as you type.

To find how much condensate a coil or dehumidifier produces in the first place, use the condensate calculator.

Methodology

The converter uses these relationships:

  • Btu/h = pints/day × 1.04 lb/pint ÷ 24 h/day × 1,055 Btu/lb
  • 1 kW = 3,412.142 Btu/h
  • 1 kW = 1,000 W
  • 1 gallon = 8 pints = 3.78541 liters
  • 1 gallon of water = 8.34 lb

Example: a dehumidifier removing 70 pints of water per day removes 70 × 1.04 ÷ 24 × 1,055 = 3,200.17 Btu/h of latent heat, or 0.94 kW. That is 70 ÷ 8 ÷ 24 = 0.3646 gallons per hour.